TS Sanitary Pressure Transmitter
- 3-A, Tri-Clamp® Sanitary Connection
- 316 Stainless Wetted parts
- Designed for “Clean-in-place” and “Sterilize-in-place” Procedures
- Media Temperatures to 250°F (121°C)
- Internal Zero & Span Adjustments
Model: TSA = General Purpose
Range: P18 = 0 -100 | P20 = 0 - 200 | P21 = 0 - 300
Output Signal: A = 4 - 20mA (2-wire)
Connection Type: TC = Tri-Clamp
Tri-Clamp Size: 15 = 1.5" Tri-Clamp
Electrical Connection: M00 = M12 x 1 (4-pin)
Mounting: DWD = Direct Mount, Welded
Fill Fluid: AG = Glycerin USP
Output Signal: 4-20mA, 2-wire (standard)
Pressure Ranges: Vacuum, compound, pressure 0/2 to 0/1000 PSI gauge and absolute. Ranges 60 psi and below not recommended with 3/4” Tri-Clamp®.
Proof Pressure | Burst Pressure | |
---|---|---|
0/5 – 0/200 psi | 3 x range | 3.8 x range |
0/300 – 0/1,000 psi | 1.75 x range | 4 x range |
Accuracy(BFSL): ±0.5% of span (standard)
Adjustment: ±5% full scale, zero & span
Input: 10-30 Vdc (for current output)
Temperature:
Temperature effect with 1.5” or 2” Tri-Clamp®:
±0.1% of span/10°F (for zero and span)
or ±0.02 psi/10°F (greater of)
Note: 3/4” tri-clamp not recommended for temperature variations. Effect is ≤ ±0.9 psi/10°F